Power cable
PWR-02XX-TC5-XZ-PF/GIS
Construction |
2C X 10 mm² |
2C X 16 mm² |
2C X 25 mm² |
Conductor |
|||
Standard |
Generally to IEC 60502-1 Class 5 Conductor |
||
Material |
Flexible Annealed Tinned Copper |
||
Max. DC Resistance @ 20°C[Ω/㎞] |
1.95 |
1.24 |
0.795 |
Cross-sectional Area[㎟] |
10 |
16 |
25 |
Insulation |
|||
Material and Color |
XLPE – Black, Blue |
||
Nominal Thickness [㎜] |
0.7 |
0.7 |
0.9 |
Diameter[mm] |
5.5±0.5 |
6.5±0.5 |
8.1±0.5 |
Laid up - Cores shall be laid-up together suitably with PP Filler |
|||
Filler |
|||
Material |
PP Filler |
||
Shielding |
|||
Material |
Galvanized Iron Wire (70% coverage) |
||
Nominal Thickness [㎜] |
0.3 ± 0.01 |
||
Outer Sheath |
|||
Material and Color |
LSZH, Black |
||
Min. Thickness [㎜] |
1.24 |
1.24 |
1.24 |
Outer Diameter [㎜] |
15.0±2.0 |
18.0±2.0 |
21.5±2.0 |
|
LS CABLE 0.6/1KV 2 X [Size in ㎟] LSZH [Year] |
||
Approx. Weight of cable [kg/km] |
390 |
570 |
800 |
Performance |
2C X 10 mm² |
2C X 16 mm² |
2C X 25 mm² |
Electrical Characteristics |
|||
Voltage rating[V] |
600 / 1,000 |
||
High Voltage test |
3.5 kV/5min. No break |
||
Environmental Characteristics |
|||
Operating temperature [℃] |
-20 ~ + 90 |
||
Flammability Test |
IEC 60332-1 |
||
Smoke emission |
IEC 61034-2 / ASTM D-2843 |
||
Oxygen index |
29% (min.) as per ASTM D-2863 |
||
Halogen Free |
IEC 60754-1 |
||
Conductivity (Conductor Resistance) Test |
IEC 60228 For Conductor |
||
Bending Radius |
12D (D : Overall Diameter of Cable) |
PWR-02XX-TC5-XVZ-GIS
Construction |
2C X 10 mm² |
2C X 16 mm² |
2C X 25 mm² |
Conductor |
|||
Standard |
Generally to IEC 60502-1 Class 5 Conductor |
||
Material |
Flexible Annealed Tinned Copper |
||
Max. DC Resistance @ 20°C[Ω/㎞] |
1.95 |
1.24 |
0.795 |
Cross-sectional Area[㎟] |
10 |
16 |
25 |
Insulation |
|||
Material and Color |
XLPE – Black, Blue |
||
Nominal Thickness [㎜] |
0.7 |
0.7 |
0.9 |
Diameter[mm] |
5.5±0.5 |
6.5±0.5 |
8.1±0.5 |
Laid up - Cores shall be laid-up together suitably |
|||
Inner Sheath |
|||
Material and Color |
PVC, Black |
||
Min. Thickness[㎜] |
0.4 |
||
Shielding |
|||
Material |
Galvanized Iron Wire (70% coverage) |
||
Nominal Thickness [㎜] |
0.3 ± 0.01 |
||
Outer Sheath |
|||
Material and Color |
LSZH, Black |
||
Min. Thickness [㎜] |
1.24 |
1.24 |
1.24 |
Outer Diameter [㎜] |
16.0±2.0 |
18.5±2.0 |
21.5±2.0 |
|
LS CABLE 0.6/1KV 2 X [Size in ㎟] LSZH [Year] |
||
Approx. Weight of cable [kg/km] |
470 |
620 |
890 |
Performance |
2C X 10 mm² |
2C X 16 mm² |
2C X 25 mm² |
Electrical Characteristics |
|||
Voltage rating[V] |
600 / 1,000 |
||
High Voltage test |
3.5 kV/5min. No break |
||
Environmental Characteristics |
|||
Operating temperature [℃] |
-20 ~ + 90 |
||
Flammability Test |
IEC 60332-1 |
||
Smoke emission |
IEC 61034-2 / ASTM D-2843 |
||
Oxygen index |
29% (min.) as per ASTM D-2863 |
||
Halogen Free |
IEC 60754-1 |
||
Conductivity (Conductor Resistance) Test |
IEC 60228 For Conductor |
||
Bending Radius |
12D (D : Overall Diameter of Cable) |